The pneumatic system supplies high pressure air for:
Ø Air
conditioning
Ø Pressurization
Ø Engine
starting
Ø Wing
anti-icing
Ø Hydraulic
reservoir pressurization
Ø Aft cargo
heat
Ø Water tank
pressurization
High pressure air can be supplied by:
Ø Engine
bleed
Ø APU load
compressor
Ø High
pressure ground connection
Controlled by BMC (Bleed Monitoring Computer)
Engine Bleeds close automatically when BMC's detect:
A APU bleed
valve open
S Engine Start
O Over
temperature
L Leak
O Over pressure
The valve will also automatically close pneumatically when:
Ø Low
pressure
Ø Reverse
flow
And is electrically closed when:
Ø ENG BLEED
selected off
Ø ENG FIRE
pb selected
The APU bleed will close for leaks
The APU is ready for bleed when reaching 95% for two seconds
or 99.5%. The AVAIL light will show in the APU start pb and green APU AVAIL
will show on EWD display when APU is available for use.
The crossbleed valve can be operated in automatic or manual
mode. There are two electric motors for the valve, one for each mode. In
automatic mode the crossbleed valve opens automatically when using APU bleed
air. During normal operation the crossbleed is closed to isolate the two engine
bleeds.
The crossbleed is manually set OPEN during the engine
crossbleed start procedure.
The leak detection system uses a single loop for the pylons
and APU to detect hot air temps associated with duct leaks. Dual loops are used
for the wings. If both of the dual loops detect a leak a warning is given,
unless there is a fault on one, then only one loop is required to give a
warning.
If a leak is detected:
Ø The engine
bleed air valve (APU bleed air valve) on that side is closed
Ø Associated
ENG (APU) BLEED FAULT light comes on
Ø Crossbleed
valve closes (except during engine start)
Ø Left wing
leak only – APU bleed air valve closes (except during ENG start)
Packs (PH
10.3.x)
i Airbus Gotcha’: Do not use external conditioned air when using packs (PH 2.9.3).
Unfortunately, there is no cockpit indication of external air connected! You
can turn off the cabin fans pb and if air continues to blow from the vents then
external air is connected.
Pay attention here, many new Airbus pilots fail to
understand the way the Zone Temp system works. If you are familiar with the
737-400 this is very similar. Both packs are feeding all three zones. Whichever
zone is commanding the coldest temperature will drive BOTH packs to that temp.
Hot air is then added to any other zone that is commanding a higher temp. This
hot air is called trim air and is how the zone temp system controls
temperatures in three zones with only two packs.
There are three air conditioning zones: Cockpit, FWD Cabin
and AFT Cabin.
The zones are controlled by having the packs deliver all air
at the lowest temp requested by any of the three zones. Then hot air is added
through the trim air valves to the other two zones as needed to meet temp
requirements. A/C zone temp selectors have a range of: Cold 18°C/64°F, 12
o’clock 24°C/76°F, Hot 30°C/86°F
The AC pack can bypass bleed air around the air cycle
machine (ACM) if the ACM fails and run the bleed air through the primary heat
exchanger directly. This allows the pack to operate as a simple heat exchanger
with reduced pack flow.
Pack flow will revert to HI during single pack operation or
APU bleed source regardless of selector position.
The Zone controller
can override pilot selected pack flow (HI, NORM and LOW) as needed to meet
demands. It can also command higher APU speed or engine idle as needed.
One Zone controller with two channels. Failure of the
primary channel will result in fixed temperature at 76° F with no optimization.
Failure of the secondary as well will result in a fixed temp of 68° F pack 1
and 50° F pack 2.
One Pack controller per pack. Two channels per controller.
If primary fails the secondary pack air flow will be fixed at the pre-failure
setting. No further optimization is available. Further failure of the secondary
will result in a fixed pack outlet temp of 59° F.
Pack controllers also regulate the cooling air flow through
the ACM. During takeoff and touchdown the controllers close the ram air inlet
flaps to prevent ingesting debris.
Note: The Airbus 319/320 can be dispatched with one pack
INOP up to FL310 or below as per MEL 21-5201A
RAM air (PH
10.3.6)
RAM air is available for cabin ventilation in the event of
loss of pressurization or smoke removal. When the RAM AIR pb is selected the
RAM air inlet opens.
When pressurization differential is less than 1 psi. the
outflow valve will open to 50% to allow exhaust. If above 1 psi. then the
outflow will remain normal.
Depressurization: When cabin exceeds about 11,000’ the cabin
may illuminate and Exit and all cabin signs illuminate automatically. Masks
will automatically drop at 14,000’ cabin altitude. (PH 15.1.3, 5.20.1)
Ventilation (PH 10.7)
The avionics are cooled through a system that uses two
openings and two electric fans. Conditioned air is also available for backup if
needed. Yes, a computer controls the whole thing (sigh).The intake is on the
lower left side below the cockpit. A blower fan draws air in and the extract
fan on the right side exhausts the air out from a port below the cockpit on the
lower right side.
Open configuration: Only for ground operations, both the
inlet and outlet vents are open and both fans operate. Note: during
heavy rain operations on ground select EXTRACT pb to OVRD with both packs
operating. This will prevent rain from entering the avionics bay. Return to
normal auto operation once airborne (see PH 3a.2 for parameters).
Closed configuration: In-flight mode and very cold ground
operations. Both vents are closed, however both fans run to circulate air past
skin heat exchangers that are cooled by low outside skin temperatures. Some air
exhausted through cargo underfloor. Also known as the infamous Skin Cooling
Config.
Intermediate configuration: Only for use in-flight when
warm, same as closed except reduced opening to allow some additional exhaust of
cooling air.
Abnormal configuration:
Fault is detected in either the BLOWER or EXTRACT fan. Blower fan is off
but Extract remains ON. Similar to closed except air conditioned air is added
to the circulated air. ECAM will direct configuration.
Smoke configuration: If smoke is detected in avionics both the BLOWER and EXTRACT fan will have amber FAULT lights on and the GEN 1 LINE pb (on EMER ELEC PWR panel) has amber SMOKE illuminated. Selecting BOTH fans to OVRD will cause the blower to stop but the extract to continue operating. Conditioned air is added to attempt to cool and clear the smoke, then exhausted overboard.